product-img
product-img
product-img
  • small-img
  • small-img
  • small-img

HY-1025

Addressable Fire Alarm Control Panel with Printer

> Two-wire and polarity-free: The system loop line adopts two-wire and polarity-free communication power supply technology without external power supply. Strong anti-interference, convenient wiring, improved system reliability and stability, easy construction and installation, reduced project cost, and convenient later stage maintenance

> Intuitive display: 480 × 272 4.3’’ LCD screen provides a highly intuitive interface, allowing the user to fully setup the system without the need of any external tool

> Ultra-long history record: Save historical events for a long time that can be inquired and printed in various ways such as time and type

> Intelligent power supply: With automatic switching between the main and backup power and the charging and discharging functions, it ensures the stable power supply of the system to the greatest extent

> Protection design: Short circuit, open circuit and overcurrent protection to ensure stable operation.

  • Especificaciones
  • Accesorios
  • Descargar
  • Technical Specification

    Main Power Supply

    AC90-240V/50Hz, 60Hz

    Backup Power

    2 lead-acid batteries (12V/5Ah each)

    Log Record

    Max. 2048

    Display Mode

    480 × 272 4.3" LCD screen

    Working Voltage

    DC 12V~48V

    Communication Mode

    Two bus line

    Platform Access

    4G, Ethernet

    Networking Mode

    RS485

    Communication Interface

    USB, RJ45, CAN, RS232, RS485, One fire alarm output and one fault output

    Load Capacity

    Loop Number: 1 or 2

    Zone Number: 0, 8 or 16

    Device Linkage Terminals: 7 groups

    Storage Capacity

    9,999 historical records

    Communication Distance

    1500 m

    Shell Material

    Chassis: Cold-rolled steel plate SPCC

    Dimensions

    550 mm×460 mm×1707 mm

    Operating Temperature

    –10°C to +55°C

    Storage Temperature

    –20°C to+65°C

    Operating Humidity

    ≤ 95% RH (no condensation)

    Compliance Standard

    EN54-2, EN54-4

    System Specification

    Loop Number

    1 loop for DHI-HY-1022(R)
    2 loops for DHI-HY-1025(R)

    Topology Mode

    Class A for DHI-HY-1022R and DHI-HY-1025R
    Class B for DHI-HY-1022 and DHI-HY-1025

    Loop Capability

    Max. 254 sensors and modules for each loop

    Optional Buit-in Micro Thermal Printer

    Option 1: With printer by default
    Option 2: Without printer by default

    Simulated Zone

    Every 32 addresses form a zone
    Applicable only to panels with a printer

    Panel Cascading

    Max. 128 panels to cascade

    Solution Verification

    With the help of Dahua Fire (Wisualarm) Presale Tool
    Performance Limitations
    Communication Distance
    Required Battery Specifications

    Configurable Alarm Linkage

    With the help of ControlConfig Tool

    IOT Solution

    Online Solution: Wisualarm Cloud Platform
    Local Solution: DSS Pro Platform V8.5-V8.7 (Server is required)

    Compatible Cable Specifications

    2X1.5mm² /2X16AWG

    Communication Distance

    1500m (standard) - 3000m (extendable)

    Telephone&Broadcast System

    Optional peripheral system