HY-C132_Image_1.png
Compare Favourite
HY-C132

Conventional Heat Detector

Key Points
    Convenient installation and debugging

Specifications

Technical Specification

Working Voltage

DC9V-DC30V

Rated Power

3.408mW

Current

Standby current: ≤ 45μA

Alarm current: ≤ 24mA

Sensor Class

A2R

Fixed Detection Threshold

62°C ± 3°C (144°F ± 37.4°F)

Dynamic Detection

1 to 30 K min-1

Alarm Mode

Visual alarm

Coverage Area

H ≤ 4 m (13.12 ft): 50 m2

4 m(13.12 ft) ≤ H ≤ 12 m(39.37 ft): 30 m2

Operating Temperature

–10°C to +50°C (+14°F to +122°F)

Operating Humidity

≤ 95% RH (no condensation)

Dimensions (with base)

Φ100 mm × 50 mm (Φ 3.00" × 2.13")

Weight (with base)

81 g (0.18 lb)

Installation

Ceiling Mount

Compliance Standard

EN 54-5

Response Time Limits

Rate of Rise of Air Temperature

Lower Limit of Response Time

Upper Limit of Response Time

K min-1

min

s

min

s

1

29

0

46

0

3

7

13

16

0

5

4

9

10

0

10

2

0

5

30

20

1

0

3

13

30

40

2

25

* Limited to a maximum of 4 products
Reset
Compare